5.1.2.1.2 SPS4 Jumper Settings
The SPS4 has two jumpers for setting its output voltage. It is factory set for 12VDC out. If
a different voltage is required, the jumpers must be changed as follows:
LeftRight5-18VDC Adjustable*
RightLeft12VDC
LeftLeft5VDC
JP2JP1Voltage Output
* - When using the adjustable range, adjust the output voltage using potentiomer R5
5.2 Visual Indicators
5.2.1 External Visual Indicators
5.2.1.1 Illuminated Power Switch / Circuit Breaker
The power switch will illuminate red when the power switch is in the “on” position and power
is present.
5.2.1.2 Front Panel Indicators
All units have front panel indicator LEDs. Each output has one LED which illuminates when
voltage is available at the corresponding output terminals.
F17
D1 D2 D3 D4 D5
D6 D7 D8 D9 D10 D11 D12 D13
D14
D15
D16
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13
F14
F15
F16
J1
J2
JP1 JP2 JP3 JP4 JP5 JP6 JP7 JP8 JP9 JP10 JP11 JP12 JP13 JP14 J P15 JP16
J3
J4
J5
J6
J7
J8
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
SPARE
38-124 Rev B
1
1
ZONES 9 - 16ZONES 1 - 8
FOR CONTINUED PROTECTION AGAINST RISK OF FIRE
REPLACE ONLY WITH SAME TYPE 3A. 32V FUSE.
UTILISER UN FUSIBLE DE RECHANGE
DE MEME TYPE 3 A 32 V
V1
V2
V1
V2
REFER TO NAMEPLATE LABEL
FOR INSTALLATION DOCUMENT
REFERENCE NUMBER
DISCONNECT SUPPLY CORD BEFORE
CHANGING FUSE
DE'BRANCHER AVANT DE REMPLACER LE FUSIBLE
ATTENTION:CAUTION:
Visual Indicators (D1-D16)
5.2.2 Internal Visual Indicators
5.2.2.1 Indicators on the internal PS5-M Board
The PS5-M contains five visual status indicators.
Lights under an Earth Ground Fault conditionYellowEarth Ground FaultGND FLT (D23)
See Section 5.2.2.1.4YellowCommon FaultCOM FLT (D16)
Lights when the AC input voltage is low or missingYellowAC FaultAC FLT (D22)
Lights when DC voltage is present on the outputGreenDC OutputDC OUT (D15)
Lights when AC voltage is present on the inputGreenAC PowerAC ON (D19)
ConditionsColorDescriptionLED
5.2.2.1.1 AC ON
For safety reasons, this LED illuminates any time there is AC voltage present at the AC
input, regardless of the AC fault status, battery state of charge, or power supply condition.
CAUTION - Always check for AC presence with a volt meter before servicing
5.2.2.1.2 DC OUT
This LED illuminates when DC voltage is available at the DC+/DC- terminals.
RMMV Series Installation Instructions
7/13/2009, 10:26:56 AM
52-391 Rev A.02
Page 13 of 20