Section 5
Operating the RMMV Rack Mount Power Supply
5.1 Jumper Configuration
5.1.1 AC Zones
Each individual AC output zone may be configured for a 24VAC or 28VAC output. The output
setting is controlled by the movable jumper plugs behind the front panel (JP1-JP16). The upper
setting (V2) is for a 28VAC output, the lower setting (V1) is for a 24VAC output.
F17
F1 F2 F3 F4 F5 F6 F7 F8 F9
J1
J2
JP1 JP2 JP3 JP4 JP5 JP6 JP7 JP8 JP9 JP10 JP11 JP12 JP13 JP14 JP15 JP16
J3
J4
J5
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
3A
3A
3A
3A
3A
3A
1
1
ZONES 9 - 16ZONES 1 - 8
FOR CONTINUED PROTECTION AGAINST RISK OF FIRE
REPLACE ONLY WITH SAME TYPE 3A. 32V FUSE.
UTILISER UN FUSIBLE DE RECHANGE
DE MEME TYPE 3 A 32 V
V1
V2
V1
V2
REFER TO NAMEPLATE LABEL
FOR INSTALLATION DOCUMENT
REFERENCE NUMBER
DISCONNECT SUPPLY CORD BEFORE
CHANGING FUSE
DE'BRANCHER AVANT DE REMPLACER LE FUSIBLE
ATTENTION:CAUTION:
Output Voltage Setting
5.1.2 DC Zones
5.1.2.1 Internal Jumper and Switch Configuration
Before powering the system, the jumpers on the internal board(s) must be set for proper
operation. Do not change jumper or switch settings while the unit is powered or damage to
the system may occur.
5.1.2.1.1 PS5-M Jumper and Switch Settings
Each unit contains one PS5-M board. The switch and jumpers need to be configured for
desired operation.
5.1.2.1.1.1 DC Voltage Setting
Before installing an RMMV system, the output voltage setting switch of the PS5-M
board must be set. Do not change the switch setting while the unit is powered or
damage to the system may occur. In the RMMV, the switch should always be set away
from the green AC visual indicator for 24V (the PC board is labeled with the voltage
settings).
RMMV Series Installation Instructions
7/13/2009, 10:26:56 AM
52-391 Rev A.02
Page 11 of 20