RMBE SeriesRack Mount Battery EnclosureOperating and Installation Instructions52-342 Rev A.01
Section 5Operating the RMBE Series5.1 Jumper Configuration5.1.1 Configuration Jumper SettingsBefore connecting the RMBE to a system, the configuratio
5.2 TroubleshootingWARNING - Installation and service should only be performed by a qualified service person andshould conform to all local codesVerif
Section 6Specifications6.1 Electrical Specifications6.1.1 Output Voltage 12VDC or 24VDC Nominal6.1.2 Amphour Capacity Varies - See Section 5.1.1.36.1.
6.3.3 CAD Drawing9.940"18.880"0.752"1.202"1.203"3.249"0.375"0.375"3.71"0.815"3.250"DETAIL “A”TY
GlossarySplitting a bulk power supply output into multiple, current limited outputs to prevent asingle circuit failure from talking down an entire sys
Warnings and NoticesWARNING - To reduce the risk of fire or electric shock, do not expose this productto rain or moistureWARNING - This installation
Table of Contents14GlossaryAppendices:126.3 Mechanical Specifications126.2 Temperature Specifications126.1 Electrical Specifications126 Specification
Section 1IntroductionThe AlarmSaf RMBE Rack Mount Battery Enclosure provides one or two 12VDC or 24VDC battery outputs in astandard 19” rack mountable
Section 2Applicable Standards / DocumentsNFPA StandardsNFPA 72 National Fire Alarm CodeNFPA 70 National Electrical CodeNFPA 731 Standard for the Insta
3.2 Terminal DescriptionsAll terminal strips are removable with locking screws and accept wire sizes from 12-26AWG. Wireshould be sized appropriately
Section 4Installation4.1 Mounting4.1.1 Mount the unit in locations that meet the following temperature and humidity requirements.Do not expose to cond
1. Note the positions of the configuration jumpers on the back panel of the enclosure andremove all jumpers. Remove any terminal strips with wiring c
4.2 Wiring4.2.1 Wire RoutingAll wiring must be installed in accordance with NFPA70 [NEC760] and all local coderequirements.Power Limited wiring requi